The minimum requirements for concrete envelope and conduit cover in underground wiring are;
- concrete envelope = minimum of 2 inches thick
- conduit cover = minimum of 24 inches thick
Requirements for Electrical Wiring
According to the 2011 NEC(National Electrical Code) requirements as pertaining to underground wiring, we are told that;
- The conduit(s) covers must be encased in a concrete envelope with a thickness of at least 2 inches.
- Secondly, the 2011 National Electrical Code) requirements also states that the cover must be at least 24 inches of cover from the top of the conduit to the grade surface.
- Finally, another key thing we see is that in a case of wire entry or exit from the ground, the method of wiring must change to another type with examples like RMC or IMC.
Read more about Requirements for Electrical Wiring at; https://brainly.com/question/9804022