Respuesta :
Answer:
COP of the heat pump is 3.013
OP of the cycle is 1.124
Explanation:
W = Q₂ - Q₁
Given
a)
Q₂ = Q₁ + W
= 15 + 7.45
= 22.45 kw
COP = Q₂ / W = 22.45 / 7.45 = 3.013
b)
Q₂ = 15 x 1.055 = 15.825 kw
therefore,
Q₁ = Q₂ - W
Q₁ = 15.825 - 7.45 = 8.375
∴ COP = Q₁ / W = 8.375 / 7.45 = 1.124
Answer:
- 3.013
- 1.124
Explanation:
W = Q2 - Q1 ----- equation 1
W = work done
Q2 = final energy
Q1 = initial energy
A) calculate the COP of the heat pump
COP = [tex]\frac{Q2}{W}[/tex]
from equation 1
Q2 = Q1 + W = 15 + 7.45 = 22.45 KW
therefore COP = [tex]\frac{22.45}{7.45}[/tex] = 3.013
B) COP when cycle is reversed
COP = [tex]\frac{Q1}{W}[/tex]
from equation 1
Q1 + W = Q2 ------ equation 2
Q2 = 15 Btu/s = 15 * 1.055 = 15.825 KW therefore from equation 2
Q1 = 8.375 KW
COP = [tex]\frac{8.375}{7.45}[/tex] = 1.124