Respuesta :
Answer:
The log-mean-temperature-difference is 24.03⁰C
Step-by-step explanation:
First we need to know if the heat exchanger is in parallel flow or counter-flow. However, counter flow arrangement is best used to recover heat.
L.M.T.D for counter flow is given as;
[tex]L.M.T.D =\frac{(T_h_f_1 -T_c_f_2)-(T_h_f_2 -T_c_f_1)}{2.3log[\frac{T_h_f_1 -T_c_f_2}{T_h_f_2 -T_c_f_1}]}[/tex]
where;
Thf₁ is the initial temperature of the hot fluid = 80°C
Tcf₂ is the final temperature of the cold fluid = 51.5°C
Thf₁ - Tcf₂ = 80 - 51.5 = 28.5⁰C
Thf₂ is the final temperature of the hot fluid = 30°C
Tcf₁ is the initial temperature of the cold fluid = 10°C
Thf₂ - Tcf₁ = 30 - 10 = 20⁰C
[tex]L.M.T.D = \frac{28.5 -20}{2.3Log[\frac{28.5}{20}]} \\\\L.M.T.D = \frac{8.5}{0.3538} =24.03^oC[/tex]
Therefore, the log-mean-temperature-difference is 24.03⁰C
Step-by-step explanation:
Below is an attachment containing the solution.