Answer:
a) W=85.225 kW
b) [tex]0.02\frac{kW}{K}[/tex]
Explanation:
First, consider the energy balance for the compressor: The energy that enters to the system (W and enthalpy of the feed flow) is equal to the energy that goes out from it (Heat Q and enthalpy of the exit flow):
[tex]W+m*h_1=Q+m*h_2\\W=Q+m*(h_2-h_1)[/tex]
Consider the enthalpy data from van Wylen 6th edition, Table B.2.2. According to that, [tex]h_1=h(200kPa,-10C)=1440.6\frac{kJ}{kgK}[/tex], [tex]h_2=h(1200kPa,140C)=1757.5\frac{kJ}{kgK}[/tex]
So, the power input to the compressor is:
[tex]W=6kW+15\frac{kg}{min}*\frac{min}{60s}*(1757.5-1440.6)\frac{kJ}{kg}\\W=85.225kW[/tex]
b) The differential entropy change dS for a reversible heat transfer dQ at a temperature T is:
[tex]dS=\frac{dQ}{T}[/tex]
This equation can be integrated if the heat transfer surface temperature remains constant, which is the case, giving as a result:
[tex]S_2-S_1=\frac{Q}{T}=\frac{6kW}{300K}=0.02\frac{kW}{K}[/tex]