1.) A 3∅ Synchronous generator is delivering 300kW, 0.65 P.F. lagging, 1800<30° Volt. The synchronous reactance is 2.7r per-phase. What is the magnitude of the line-current from the generator at rated full load?
Hint: Draw the 1∅ equivalent of the 3∅. Note that 300kW is a 3∅ specification and 1800<30° Volt is a line voltage.
A.) 85.47 A
B.) 96. 225 A
C.) 148.04 A
D.) 55.56 A